Conventional Photoelectric Smoke and Heat Alarm
需要先拿到样品,联系我们!
查看类似产品
标签列表
- 产品描述
-
Conventional Heat Detector
All of the SD119 series detectors meet the requirements of UL 268 and EN 54-7/5 for use in fire alarm signaling systems. They are intended for use in 2-wire/4-wire Class A or B supervised zone circuits. The SD119 series detectors are subject to panel compatibility limits and compliance with corresponding NFPA 72E standards, local codes, and ordinances.
The SD119 series include 2-wire and 4-wire detectors, which provide fast and reliable response for photoelectric smoke and heat (135°F) detection. While the smoke and heat detection circuits operate independently, their outputs being "OR' connected, The SD119 series detectors provide the fire detection performance by acting as a smoke sensor and/or a 13°F heat detector at the same location.
Product Features:
- 2 or 4 wire models
- Advanced detection and discrimination algorithms
- Easy installation and maintenance
- Sleek low-profile housing design
- Durable sensor head, no need for replacement
- SMD circuit board design-satisfactory quality and reliability guaranteed
- Integrated heat detector for SD119-2H and SD119-4H models
- N/C (normal/close)-N/O (normal/open)selectable relay output
- AR (Auto Reset) function for security systems (optional for 4 wire models) Sensor base option: standard and Shottky Diode
- Five-year limited warranty
The range includes:
SD119- 2
2 wire photoelectric smoke alarm
SD119- 2- LED
2 wire photoelectric smoke alarm with remote LED output
SD119- 2H
2 wire photoelectric smoke and heat alarm
SD119- 2H- LED
2 wire photoelectric smoke and heat alarm with remote LED output
SD119- 4
4 wire photoelectric smoke alarm (12/24/48VDC)
SD119- 4B
4 wire photoelectric smoke alarm with Buzzer (12/24/48VDC)
SD119- 4AR
4 wire photoelectric smoke alarm with auto-reset function (12/24/48VDC)
SD119- 4ARB
4 wire photoelectric smoke alarm with auto-reset function and Buzzer (12/24/48VDC)
SD119- 4H
4 wire photoelectric smoke and heat alarm (12/24/48VDC)
SD119- 4HB
4 wire photoelectric smoke and heat alarm with Buzzer (12/24/48VDC)
SD119- 4HAR
4 wire photoelectric smoke and heat alarm with auto-reset function (12/24/48VDC)
Product Data:
Smoke Sensitivity:
0.08~0.2db/m(EN standard) or 0.98~4.0%/FT Obscuration (UL standard)
Ceiling Spacing:
50 foot rating for heat sensor
Reset Voltage:
less than 1 volt
Reset Time:
less than 1 second
Alarm Indicator:
LED continuously emitting red light
Remote Output:
25 mA max., diode gate
Temperature Range:
-10°C to 55°C, UL268 temperature: 0~37.8°C
Permissible Current:
80mA maximum
Humidity:
0 to 95% RH, no condensation or icing
Alarm Contact:
(for 4-wire) NO or NC Operation, Form A: 1.0A@30VDC/0.5A@125VAC
Dimensions:
100mm (dia) x 46mm (ht) with base
Weight:
130g/set with base